Alarm log function – IDEC High Performance Series User Manual

Page 813

Advertising
background image

WindO/I-NV2 User’s Manual

13-15

3 Alarm Log Settings Dialog Box

13

Alarm Log Function

Monitoring Period (x 100 msec)
Specifies the period to write the state of the monitored device to the MICRO/I (6 to 500 (100 ms units)).

Monitor Number of Active Alarms
Select this check box to count the number of active alarms.

Monitor How Many Times Each Alarm has occurred
Select this check box to count the number of alarms that has occurred per channel.

Clear Log Data for Recovered Alarms
Select this check box to delete recovered data out of the saved Alarm Log data.

Monitor the State of Each Alarm
Select this check box to check the alarm state per channel.

The following values are written to the bits depending on the alarm state.

(Destination Device): Specifies a word device to write the number of active alarms.

For the device address configuration procedure, refer to Chapter 2 “5.1 Device Address Settings”
on page 2-67.

(Top Device):

Specifies a word device to write the number of alarms that has occurred. Number of blocks x 16
(number of channels) addresses are used starting from the set device address.
For the device address configuration procedure, refer to Chapter 2 “5.1 Device Address Settings”
on page 2-67.
Example: When the number of blocks is 2 and LKR 100 is specified as the start device

The number of alarms that has occurred for channel number 1-0 is saved in LKR 100.
The number of alarms that has occurred for channel 1-1 is saved in LKR 101, and this
pattern continues up to LKR 131 where the number of alarms that has occurred for
channel number 2-15 is saved.

Top device

Block 1

16 channels

Block 2

16 channels

Channel No.

LKR100
LKR101
LKR102

LKR114
LKR115
LKR116
LKR117
LKR118

LKR130
LKR131

1-0
1-1
1-2

1-14
1-15
2-0
2-1
2-2

2-14
2-15

• If you specify HG keep registers (LKR) as the destination word device, the number of alarms that has

occurred is retained even when the MICRO/I power is turned off.

• The amount of Alarm Log data saved in the data storage area with the Alarm Log function is stored in HG

special register LSD 57.

• To monitor the number of alarms that has occurred, number of blocks x 16 (number of channels) devices

are required from the set start device. If the destination device does not exist, “Device range error”
occurs on the MICRO/I.

• If the values of the devices that are counting the number of alarms that has occurred are overwritten by

another process, the alarms cannot be accurately counted.

(Trigger Device):

Specifies the bit device or bit of the word device to serve as condition to delete data. The recovered
data is deleted when the value of the configured device changes from 0 to 1. For the device address
configuration procedure, refer to Chapter 2 “5.1 Device Address Settings” on page 2-67.

(Top Device):

Specifies a word device to write the alarm state. Number of blocks x 16 (number of channels)
addresses are used starting from the set device address.
For the device address configuration procedure, refer to Chapter 2 “5.1 Device Address Settings”
on page 2-67.

Bit 15

Bit 0

Bit 3

0: Before alarm/aŌer recovery
1: AŌer alarm

0: Second and later alarm (Alarm that has occurred again while an alarm is acƟve)
1: First alarm (First alarm that occurred)

0: AŌer confirm
1: Before confirm

Reserved