Options tab, Data displa ys, Windo/i-nv2 user’s manual – IDEC High Performance Series User Manual

Page 625: 7 alarm list display

Advertising
background image

WindO/I-NV2 User’s Manual

10-113

7 Alarm List Display

10

Data Displa

ys

Options Tab

The Options tab is displayed in Advanced mode.

Reference Screen
The Options tab is used to configure the reference screen. The reference screen is a base screen or popup screen
associated with each individual message. The reference screen is displayed when the key button Ref. is pressed.

When displaying a reference screen, select either Base Screen or Popup Screen as the reference screen type.
When not displaying a reference, select Not Use.
This can only be set when New Message List has been selected in Message Settings on the General tab. When
Use Alarm Log Settings has been selected, the screen type will become the one selected in Reference Screen on
the Channel tab in the Alarm Log Settings dialog box.

Coordinates

(Reference screen list)

Motor fault

Pump1 fault

REV

Up

Dwn

Del

Ref.

High pressure

Pump 1 fault

Motor fault

Pump1 fault

REV

Up

Dwn

Del

Ref.

High pressure

Pump 1 fault

Motor fault

Pump1 fault

REV

Up

Dwn

Del

Ref.

High pressure

Pump 1 fault

Key buƩon Ref.

Reference screen

Key buƩons Up and Dwn

1. Select a message displayed

on the Alarm List Display

2. Press the key buƩon Ref.

Reference screen opens

Pump 1 fault

Pump 1 fault

Pump 1 output low

Stop

Start

Press Stop, check the air,
then press Start.

Air Press.

kg/m

2

0000

X, Y:

Specifies the coordinates to display the reference screen.
With the upper-left corner of the screen as the origin, the X and Y coordinates are the upper-left corner of the
reference screen.
This option can only be configured when Base Screen or Popup Screen is selected for Reference Screen.

HG2G-S/-5S/-5F, HG3G/4G, HG1F:

Specify the coordinates in 1 dot units.
X: 0 to (base screen horizontal size - 1)
Y: 0 to (base screen vertical size - 1)

HG2F/2S/3F/4F:

Specify the coordinates in 20 dot units.
X: 0 to (base screen horizontal size - 20)
Y: 0 to (base screen vertical size - 20)

Advertising