3 Preventive Maintenance Settings Dialog Box

17-8

WindO/I-NV2 User’s Manual

3.2 Individual Settings Dialog Box

The Individual Settings dialog box is used to configure the operation time and operation count settings for each
monitored device.

Operation Time Tab

The Operation Time tab is used to configure the destination device for the counted operation time and the report
conditions when the threshold is reached or exceeded.

Measure Operation Time
Select this check box to count the operation time.

Data Type
Select the data type for the operation time device as BIN16 (+) or BIN32 (+). For details, refer to Chapter 2 “1.2
Available Data” on page 2-2.

Report when Operation Time has reached or exceeded Threshold level
Select this check box to report when the counted operation time reaches or exceeds the threshold.

(Data Type)
Selects the type of data for the threshold.

Level 1
Configures the level 1 threshold and report device.

No.:

Shows the number selected in Settings in the Preventive Maintenance Settings dialog box.
To change the set number, specify a number (1 to 256).
You can only specify a number of the amount of devices configured by Number of Items in
the Preventive Maintenance Settings dialog box.

Monitor Device:

Specifies the bit device or bit of the word device to count the operation time or operation count.
Click

to display the Device Address Settings dialog box. For the device address

configuration procedure, refer to Chapter 2 “5.1 Device Address Settings” on page 2-67.

(Operation Time Device): Specifies the destination device for the counted operation time. You can only specify an

HG keep register (LKR).
Click

to display the Device Address Settings dialog box. For the device address

configuration procedure, refer to Chapter 2 “5.1 Device Address Settings” on page 2-67.

If you specify the same device as the operation time device for multiple numbers, the counted operation
time is added in total by all the monitored devices for each number and the function will not be able to
count normally.

Value:

Uses a constant as the threshold.

Device:

Uses a device value as the threshold.

Threshold

Specifies the time as a constant or a device that is the criterion for reporting at level 1. For a
constant, the range that can be set varies based on the data type. For a device, click

to

display the Device Address Settings dialog box. For the device address configuration
procedure, refer to Chapter 2 “5.1 Device Address Settings” on page 2-67.