Serial interface (com2), Expansion module interface (ext) – IDEC High Performance Series User Manual

Page 1336

Advertising
background image

2 HG2G-5F, HG3G/4G

34-20

WindO/I-NV2 User’s Manual

Serial Interface (COM2)

• Terminating Resistor Selector Switch (for RS485(422) interface)

When using RS485(422) interface, set the Terminating Resistor Selector Switch to the ON side. This will connect the
internal terminating resistor (120Ω) between RDA and RDB.

Expansion Module Interface (EXT)

IDEC MICROSmart expansion modules can be connected to the HG2G-5F, HG3G/4G.

HG2G: Up to two modules
HG3G/4G: Up to four modules

Refer to Chapter 29 “1.2 Applicable Expansion Modules” on page 29-2 for the types and the combination of the
expansion modules that can be installed.

Interface Specification

RS232C/485(422)

Connector

Detachable Terminal Block 9 pin

Applicable cable

AWG16 to AWG28

Recommended Pressure Terminal

AI 0.25-6 BU
AI 0.34-6 TQ
AI 0.5-8 WH
AI 0.75-8 GY
AI 1-8 RD
(Phoenix Contact)

Tightening Torque

0.22 to 0.25 N•m

No.

Name

I/O

Function

Communication type

1

SD

OUT

Send Data

RS232C

2

RD

IN

Receive Data

3

RS

OUT

Request to Send

4

CS

IN

Clear to Send

5

SG

Signal Ground

RS485(422)

6

4W-SDA

OUT

Send Data (+) [4W]

7

4W-SDB

OUT

Send Data (-) [4W]

8

4W-RDA/2W-A

IN/INOUT

Receive Data (+) [4W]/ Send and Receive Data
(+) [2W]

9

4W-RDB/2W-B

IN/INOUT

Receive Data (-) [4W]/ Send and Receive Data (-)
[2W]