Data log function – IDEC High Performance Series User Manual

Page 875

Advertising
background image

WindO/I-NV2 User’s Manual

14-37

4 Using the Data

14

Data Log Function

Example 2: When the amount of data is less than the data to copy
When the sampling time and values of devices from data start number 1 to end number 3 are copied to the
destination device as two items of data

Item

Setting

Destination Device

LDR 10

Starting Point

Newest Data

Number of Data

2

Stored Order of Data

From Oldest to Newest

Target Data

Sampling Time, Value of Device

Data No.: Start No. 1, End No. 3

When writing with the following settings, “Device range error” is displayed.

Starting Point is 0 or a value larger than the amount of saved data
Start No. is 0 or a value larger than Data No.
End No. is 0 or a value larger than Data No.
Start No. is a value larger than End No.

Data log data

Sampling Time

Data 1

Data 2 Data 3 (no data)

10/01/2011 12:00:30

10

40

10/01/2011 12:34:56

100

60

10/02/2011 03:45:12

200

80

Newest Data read starting point

Destination Device

Value

Configured device

LDR 10

2011

Copy from oldest data

LDR 11

10

First sampling time

LDR 12

01

LDR 13

12

LDR 14

34

LDR 15

56

LDR 16

2011

Second sampling time

LDR 17

10

LDR 18

02

LDR 19

03

LDR 20

45

LDR 21

12

LDR 22

100

First data 1 value

LDR 23

200

Second data 1 value

LDR 24

60

First data 2 value

LDR 25

80

Second data 2 value

LDR 26

0

First data 3 value

LDR 27

0

Second data 3 value

1.

2.

3.

4.

1.

2.

3.

4.

If the amount of data in the Data Log is less

than the data to copy, 0 is stored