7 installation, Operating environment, Ambient temperature – IDEC High Performance Series User Manual

Page 1381: Hg3/4f installation, Installation -65, Micro/ i specif ication s, Caution

Advertising
background image

WindO/I-NV2 User’s Manual

34-65

5 HG3F/4F

34

MICRO/

I Specif

ication

s

5.7 Installation

Operating Environment

For designed performance and safety of the HG3/4F, do not install the HG3/4F in the following environments:

• Where dust, briny air, or iron particles exist.
• Where oil or chemical splashes for a long time.
• Where oil mist is filled.
• Where direct sunlight falls on the HG3/4F.
• Where strong ultraviolet rays fall on the HG3/4F.
• Where corrosive or combustible gasses exist.
• Where the HG3/4F is subjected to shocks or vibrations.
• Where condensation occurs due to rapid temperature change.
• Where high-voltage or arc-generating equipment (electromagnetic contactors or circuit protectors) exists in the

vicinity.

Ambient Temperature

• Allow sufficient space for ventilation, and install the equipment away from heat sources.
• Allow at least 100mm between the HG3/4F and walls or other equipment.
• Do not install the HG3/4F where the ambient temperature exceeds the rated operating ambient temperature range.

When mounting the HG3/4F in such locations, provide a forced air-cooling fan or air-conditioner to keep the
ambient temperature within the rated temperature range.

HG3/4F Installation

• Make a panel cut-out on the panel with the dimensions shown below.

• Place the HG3/4F in a panel cut-out and fasten with the attached mounting clips at four places to a torque of 0.4 to

0.6 N•m uniformly.

CAUTION

• Do not tighten excessively, otherwise the HG3/4F may warp and cause wrinkle on the display, or

impair the waterproof characteristics.

• If the mounting clips are tightened obliquely to the panel, the HG3/4F may fall off the panel.
• When installing the HG3/4F into a panel cut-out, make sure that the gasket is not twisted.

Especially when re-installing, take special care because any twists in the gasket will impair the
waterproof characteristics.

B

A

Unit: mm

Type No.

A

B

Panel Cut-out

HG3F

228.0

+0.5
0

302.0

+0.5
0

2.0 to 5.0

HG4F

258.0

+1.0
0

332.0

+1.0
0

2.0 to 5.0

HG3/4F

Mounting

Clip

Mounting

Clip

Panel

Advertising