Data log function – IDEC High Performance Series User Manual

Page 855

Advertising
background image

WindO/I-NV2 User’s Manual

14-17

3 Data Log Settings Dialog Box

14

Data Log Function

Sampling Method
Sets the condition for sampling device values.

Monitor Sampling Count

*2

Select this check box to monitor the number of times devices values are sampled. The sampling count is written to
the specified device.

Monitor % Space Used in Data Storage Area

*2

Select this check box to monitor the usage of the allocated data storage area as the save destination for Data Log
data. The usage is calculated from the data storage amount allocated to the data storage area and the amount of
saved data, and then written to the specified device.

Usage = Current amount of Data Log data ÷ Data Log data storage amount per device (omits values after the decimal point)

*1 HG2G-5F, HG3G/4G only
*2 HG2G-S/-5S/-5F, HG3G/4G only
*3 Advanced mode only

Fixed Period:

Samples the value of source device at a fixed interval.
Time (sec):

Specifies the time in seconds (1 to 9999).
This option can only be set when Fixed Period is selected.

Event Bit:

Samples the value of source device each time the bit device or word device bit changes from 0 to 1.

Event Word:

Samples the value of source device each time the value of word device changes.

Data Size

*1

:

Selects the data size of the monitored device as 16-bit or 32-bit.
This option can only be set when Event Word is selected.

Device:

Specifies the word device that triggers sampling data.
For the device address configuration procedure, refer to Chapter 2 “5.1 Device
Address Settings” on page 2-67.
This option can only be set when Event Bit or Event Word is selected.

Data for channels with different sampling methods cannot be displayed in the Line Chart.

(Destination Device): Specifies the destination word device.

For the device address configuration procedure, refer to Chapter 2 “5.1 Device Address
Settings” on page 2-67.

Report when Sampling Count has reached or exceeded Threshold

*3

:

Writes 1 in the report device when the current sampling count reaches or
exceeds the set threshold.

Threshold

*3

:

Specifies the sampling count that is the basis for reporting.

HG2G-S/-5S:

1 to 13808

HG2G-5F, HG3G/4G:

1 to 29165

Report Device

*3

: Specifies the destination bit device or the bit in the destination word device.

For the device address configuration procedure, refer to Chapter 2 “5.1 Device
Address Settings” on page 2-67.

(Destination Device): Specifies the destination word device to write the current usage of the amount of Data Log data

storage.
For the device address configuration procedure, refer to Chapter 2 “5.1 Device Address
Settings” on page 2-67.

Report when % Space Used has reached or exceeded Threshold

*3

:

Writes 1 in the report device when the current usage reaches or exceeds the
set threshold.

Threshold

*3

:

Specifies the usage (1 to 100) that is the basis for reporting.

Report Device

*3

: Specifies the destination bit device or the bit in the destination word device.

For the device address configuration procedure, refer to Chapter 2 “5.1 Device
Address Settings” on page 2-67.