3 data log settings dialog box, 1 data log settings dialog box, Data log settings dialog box -13 – IDEC High Performance Series User Manual

Page 851: Data log function, 3data log settings dialog box

Advertising
background image

WindO/I-NV2 User’s Manual

14-13

3 Data Log Settings Dialog Box

14

Data Log Function

This section describes the items and buttons on the Data Log Settings dialog box and the Individual Settings dialog
box.

3.1 Data Log Settings Dialog Box

All the devices to sample values from and their sampling conditions are collectively managed in the Data Log
Settings
dialog box.

Settings
Edits the Data Log settings for each channel.

*1 HG2G-5F, HG3G/4G only

3

Data Log Settings Dialog Box

HG3G

HG2G-5F

HG2G-5S

HG2G-S

HG4G HG1F HG2F HG2S HG3F HG4F

Channel No.:

Shows the channel number. Double clicking the cell displays the Individual Settings dialog
box where you can edit the settings. For details, refer to “3.2 Individual Settings Dialog Box” on
page 14-16.

Log function:

Shows whether or not the Data Log function is used. Double clicking the cell switches between
Enable and Disable. If switched to Disable, that channel’s settings all return to the default
settings.

Data Size

*1

:

Shows the data size for the source device. Double clicking the cell switches between 16-bit and
32-bit. This option can only be set when Enable is selected in Log Function.

Source:

Specifies the device to sample values from. Double clicking the cell displays the Device
Address Settings
dialog box where you can edit the device address. For the device address
configuration procedure, refer to Chapter 2 “5.1 Device Address Settings” on page 2-67. This
option can only be set when Enable is selected in Log Function.

Sampling Method:

Shows the condition for sampling data. Double clicking the cell switches between Fixed Period,
Event Bit, and Event Word. This option can only be set when Enable is selected in Log Function.

Data Size

*1

:

Shows the data size for the device that is the sampling condition. Double clicking the cell
switches between 16-bit and 32-bit. This option can only be set when Event Word is
selected in Sampling Method.

Range:

Shows the time in seconds (1 to 9999) to sample data in a fixed interval when Fixed Period is
selected in Sampling Method. Double clicking the cell displays the Individual Settings dialog box
where you can edit the settings. For details, refer to “3.2 Individual Settings Dialog Box” on page 14-
16.
Shows the device that is the condition for sampling data when Event Bit or Event Word is
selected in Sampling Method. Double clicking the cell displays the Device Address Settings
dialog box where you can edit the device address. For the device address configuration
procedure, refer to Chapter 2 “5.1 Device Address Settings” on page 2-67.