1.4 Script Error

This section describes the types, cause, and information of script errors.

Error information

Script error information is stored in the following locations. An error message is displayed on the screen when a script
error has occurred.

Types and causes of script errors

Script will stop running when an error occurs.

Category

Storage location

Stored value

Existence of a script error

Bit 10 of the System Area address
+2

0

No error

1

Error

Script ID of the script with an error HG Special Register LSD 52

1 to

32,000

Script ID

Types of script errors

HG Special Register LSD 53

1

Processing error

2

Execution time over error

3

Writing count error

4

Indirect device error

5

Parameter error

6

Fixed Interval Script execution time over

7

Fixed interval execution error

If there is a script error, bit 10 (11th bit) of the beginning device +2 (third word from the beginning) of the
System Area will be 1.

Beginning device of the System Area is set in the System tab of the Project Settings dialog box.
For details about the System Area, refer to Chapter 4 “System Area” on page 4-32.

Beginning device

+1

+2

+3

+4

+5

+6

+7

System Area 1

System Area 2

System Area 3

System Area 4

+8

+9

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

1st word

2nd word

11th bit

3rd word

4th word

5th word

6th word

8th word

7th word

10th word

9th word

Types of script error

Cause

Processing error

Dividend was divided by 0 for division and residue calculation.

Data types are BCD, float32, and value out of range is specified.

Execution time over error

The execution time for one script exceeded the following limit.

HG2G-5F, HG3G/4G: 3,000 milliseconds
HG2G-S/5S, HG1F/2F/2S/3F/4F: 500 milliseconds

Fixed Interval Script execution time
over

Writing count error

Data count written to the external device address in one script has exceeded 64.

Indirect device error

Indirect read from external device address is performed while the HG Special
Relay LSM14 or LSM15 is 1.

Indirect read or indirect write of external device address is performed with the
Global Script.

Parameter error

Value out of range was specified as argument for LINE function, RECTANGLE
function, or CIRCLE function.

Executed the LINE function, RECTANGLE function, and CIRCLE function in a Cyclic
Script.

Fixed interval execution error

Execution interval is automatically adjusted since the execution of the Fixed
Interval Script has taken more time than half of the execution interval specified
in the Fixed Interval Script.