Project set tings – IDEC High Performance Series User Manual

Page 221

Advertising
background image

WindO/I-NV2 User’s Manual

4-35

3 Project Settings Dialog Box

4

Project Set

tings

System Area 3

This area is for changing the MICRO/I internal clock data.

System Area 4

This area reads the MICRO/I internal clock data in one minute intervals.

Address

Bit

Function

Description

+3

3

Printing

This bit changes to 1 when sending output to the printer. This bit

automatically changes to 0 when finished sending output.

4

Transferring recipe

This bit changes to 1 when transferring recipe data. This bit

automatically changes to 0 when the transfer is finished.

5

Character input setting
complete

This bit changes to 1 when finished entering text with the

Character Input. Write 0 to character input setting clear

(address+1, bit 11) to clear this bit.

6

Character input setting cancel

This bit changes to 1 when entering text with the Character Input

is canceled. Write 0 to character input setting clear (address+1,

bit 11) to clear this bit.

7 to 15

Reserved

Address

Bit

Function

Description

+4

0 to 7

Clock data Month

Enter Month (01 to 12) as a 2 digit BCD.

8 to 15

Clock data Year

Enter Year (00 to 99) as a 2 digit BCD.

+5

0 to 7

Clock data Hour

Enter Hour (00 to 23) as a 2 digit BCD.

8 to 15

Clock data Day

Enter Day (01 to 31) as a 2 digit BCD.

+6

0 to 7

Clock data Second

Enter Second (00 to 59) as a 2 digit BCD.

8 to 15

Clock data Minute

Enter Minute (00 to 59) as a 2 digit BCD.

+7

0 to 14

Reserved

Enter 0 in the reserved area.

15

Update

Write 1 to this bit to write the entered data (address+4 to +6, bits

0 to 15) to the MICRO/I internal clock data.

When the value of the update bit (address+7, bit 15) becomes 1, the clock data is updated as a whole.
Year, month, day, hour, minute, and second cannot be set individually.

Address

Bit

Function

Description

+8

0 to 7

Clock data Month

These bits store the current Month (01 to 12) value as a 2 digit BCD.

8 to 15

Clock data Year

These bits store the current Year (00 to 99) value as a 2 digit BCD.

+9

0 to 7

Clock data Hour

These bits store the current Hour (00 to 23) value as a 2 digit BCD.

8 to 15

Clock data Day

These bits store the current Day (01 to 31) value as a 2 digit BCD.

+10

0 to 7

Reserved

8 to 15

Clock data Minute

These bits store the current MICRO/I clock data Minute (00 to 59).

+11

0 to 3

Clock data Day of Week

These bits store the current Day of Week value as a 2 digit BCD. The

relationship between the day of the week and the value is as follows.

00: Sunday

01: Monday

02: Tuesday

03: Wednesday

04: Thursday

05: Friday

06: Saturday

4 to 15

Reserved

Advertising