4 external interfaces, Serial interface 1, External interfaces -4 – IDEC High Performance Series User Manual

Page 1320: Caution

Advertising
background image

1 HG2G-S/-5S

34-4

WindO/I-NV2 User’s Manual

1.4 External Interfaces

Serial Interface 1

• Terminating Resistor Selector Switch (for RS485(422) interface)

When using RS485(422) interface, set the Terminating Resistor Selector Switch to the ON side. This will connect the
internal terminating resistor (100Ω) between RDA and RDB.

CAUTION

• Make sure to turn off the power to the HG2G-S/-5S before wiring each interface or switching the

terminating resistor selector Switch.

• Note that only one of the RS232C or RS485(422) interfaces can be used at one time. Wiring both

interfaces will result in failure of the HG2G-S/-5S. Wire only the interface used.

Interface Specification

RS232C/485(422)

Connector

Detachable Terminal Block 9 pin

Applicable cable

AWG16 to AWG28

Recommended Pressure Terminal

AI 0.25-6 BU
AI 0.34-6 TQ
AI 0.5-8 WH
AI 0.75-8 GY
AI 1-8 RD
(Phoenix Contact)

Tightening Torque

0.22 to 0.25 N·m

No.

Name

I/O

Function

Communication type

1