Communic ation – IDEC High Performance Series User Manual

Page 143

Advertising
background image

WindO/I-NV2 User’s Manual

3-41

5 User Communication

3

Communic

ation

Variable
Select this check box to change the transmitted data size according to conditions. This can be configured only when
No Conversion is selected under Conversion Type. When the check box is not selected, the amount of data
(bytes) transmitted is data (bytes) for Number of bytes x Words.

Examples: Device for transmission command data

Example 1

When the trigger condition is satisfied, the value of device is read and data is transmitted in the following order.

Example 2

When the trigger condition is satisfied, the value of device is read and data is transmitted in the following order.

NULL (00h):

Send the data from the start data of the value of device up to 00 (hexadecimal). Data 00 will not
be sent. This setting is effective for sending only the character data section of character data
having 00 (hexadecimal) as the last data.

Device:

Specify a word device to which a number of bytes is applied for transmitted data.

Click

to display the Device Address Settings dialog box. For the device address configuration

procedure, refer to Chapter 2 “5.1 Device Address Settings” on page 2-67.
When the value of device exceeds Number of bytes x Words, or when it is negative, the Device
Data Variable Specification Error (address+0, bit 6) of the Status Device changes to 1, and
transmission does not occur.

Item

Setting

Conversion Type

No Conversion

Device

LDR100

Use Reference Device

OFF

Storage Method of data

from Upper byte

Number of bytes

1

Words

3

Variable

OFF

Item

Setting

Conversion Type

No Conversion

Device

LDR100

Use Reference Device

OFF

Storage Method of data

from Lower byte

Number of bytes

2

Words

3

Variable

OFF

1234h

LDR100:

5678h

LDR101:

9ABCh

LDR102:

No conversion

12h

Upper

Lower

Value of Device

34h

56h

78h

9Ah

BCh

from Upper byte

1 byte

Transmission data

12h

56h

9Ah

Order of transmission

Words: 3

LDR100:
LDR101:

Transmission data

34h

12h

78h

9ABCh

LDR102:

9Ah

BCh

56h

BCh

9Ah

Order of transmission

1234h
5678h

12h

34h

56h

78h

No conversion

Upper

Lower

Value of Device

from Lower byte

2 bytes

Words: 3

Advertising