2 USB Flash Drives

30-34

WindO/I-NV2 User’s Manual

command = LDR_DOWNLOAD

src_path (required)
Specify the path (250 or less characters) where the PLC program file is to be downloaded.
Use “A:\” for an SD memory card and “B:\” for a USB flash drive.

dst_port (required)

dst_net_no (required when specifying the destination as a network number or station number)
Specify the network number or station number of the download destination PLC. Specify the same number set as the
network number or station number for the PLC.

dst_plc_ip (required when specifying the destination as an IP address)
Specify the IP address of the download destination PLC.
Example: dst_plc_ip = 192.168.0.1

dst_plc_port
Specify the port number of the download destination PLC.
Example: dst_plc_port = 2101

command = LDR_UPLOAD

dst_path (required)
Specify the path to the folder (250 or less characters) where the uploaded PLC program file will be saved.
Use “A:\” for an SD memory card and “B:\” for a USB flash drive.

src_port (required)

src_net_no (required when specifying the destination as a network number or station number)
Specify the network number or station number of the upload source PLC. Specify the same number set as the
network number or station number for the PLC.

src_plc_ip (required when specifying the destination as an IP address)
Specify the IP address of the upload source PLC.
Example: src_plc_ip = 192.168.0.1

src_plc_port
Specify the port number of the upload source PLC.
Example: src_plc_port = 2101

Specify the name of the MICRO/I port to which the PLC to download from is connected.
COM1:

Serial interface (COM1) (D-sub 9-pin)

COM2:

Serial interface (COM2) (terminals)

ETHER:

Ethernet interface (LAN)

When specifying the destination as an IP address and this item is left blank or contains an illegal value, the
MICRO/I assumes that the value is "2101". This item is not required when specifying the destination as a
network number or station number.

Specify the name of the MICRO/I port to which the PLC to upload from is connected.
COM1:

Serial interface (COM1) (D-sub 9-pin)

COM2:

Serial interface (COM2) (terminals)

ETHER:

Ethernet interface (LAN)

When specifying the destination as an IP address and this item is left blank or contains an illegal value, the
MICRO/I assumes that the value is "2101". This item is not required when specifying the destination as a
network number or station number.