Rec ipe func tion – IDEC High Performance Series User Manual

Page 931

Advertising
background image

WindO/I-NV2 User’s Manual

18-5

2 Recipe Function Configuration Procedure

18

R

ec

ipe

Func

tion

4

On the Channel tab, under Recipe Function, select Enable.
The channel for the block number displayed in Channel is enabled.

5

Enter the name for the Recipe function in Recipe Name.
The maximum number is 40 characters.

6

Specify the destination device for the Recipe values in Top Device.
To read device values and save them as a recipe file, specify the source device of the values.

Click

to display the Device Address Settings dialog box.

For the device address configuration procedure, refer to Chapter 2 “5.1 Device Address Settings” on page 2-67.
The specified device addresses are configured sequentially from the number 1 in Data List on the Data tab.

7

Select the data type for the values to write with Data Type.
To read device values and save them as a recipe file, specify the type of data for the read values.

8

With Number of Data, specify the number of destination devices starting with the device address configured by Top
Device
.
To read device values and save them as a recipe file, specify the number of source devices.
The sequential devices from the start address for the number of configured devices is displayed in Settings on the
Data tab.
The amount of data that can be set varies based on the data type. When BIN16 (+), BIN16 (+/-), or BCD4 is
selected for Data Type, up to 8192 items of data can be configured. When BIN32 (+), BIN32 (+/-), or BCD8 is
selected, up to 4096 items of data can be configured.

9

With Display Type, select the display type for Data to configure in Data List on the Data tab.
To save data to a recipe file, the display type is decimal for all.

Advertising
This manual is related to the following products: