5 saving and deleting data, Saving data, Saving and deleting data -7 – IDEC High Performance Series User Manual

Page 805: Alarm log function

Advertising
background image

WindO/I-NV2 User’s Manual

13-7

1 Overview

13

Alarm Log Function

1.5 Saving and Deleting Data

Saving Data

You can select whether or not to save the sampled data in the data storage area. The method to save data is
configured on the Channel tab in the Alarm Log Settings dialog box.

When Saving Data to the Data Storage Area

Select Store under Data in the Auto-Setup dialog box or in the Individual Settings dialog box.

If the number of active alarms exceeds the Alarm Log data storage amount set for the data storage area, the data is
processed with either of the following methods.

Fixed
If the saved data exceeds the Alarm Log data storage amount, the new data is not saved.

Rotate
If the saved data exceeds the Alarm Log data storage amount, the oldest data is deleted and the new data is saved.

MICRO/I

Host

0

1

12:00

0

1

12:53

12:00
Alarm occurred

12:53 Recovered

12:54 Confirmed

Alarm Log data

No.

Message

Occurrence Time

Recovery Time

ConfirmaƟon Time

1-1

Voltage drop

12/01/2011 12:00:00

12/01 12:53:10

12/01 12:54:30

Alarm Log data storage amount

New data

Alarm Log data storage amount

Oldest data

(delete)

New data

When the backup battery is depleted and for the HG2G-5ST22VF-*, the data in the Alarm Log is erased
when the MICRO/I is turned off.