WindO/I-NV2 User’s Manual

14-35

4 Using the Data

14

Data Log Function

Copying Data when 32-bit is Selected as the Data Size

When 32-bit is selected for Data Size on the General tab on the Individual Settings dialog box, two destination
devices are required for a single item of data.

Example 1
Copying the newest data in the Data Log with the data size selected as 32-bit to the destination device LDR 10.

Item

Setting

Destination Device

LDR 10

Starting Point

Newest Data

Number of Data

2

Data Size

32-bit

Stored Order of Data

From Newest to Oldest

Data log data

Sampling Time

Value

Destination Device Value

12/18/2011 17:44:10

87654321

(hex)

Configured device

LDR 10

3344

Copy from newest data

LDR 11

1122

2

1

R

D

L

:

:

7788

12/19/2011 19:24:43

12345678

(hex)

LDR 13

5566

12/19/2011 20:01:54

55667788

(hex)

Newest data
read starting point

12/19/2011 21:39:21

11223344

(hex)

Amount of data: 2

The data copy order for the device selected with a data size of 32-bit is configured on the Project Settings
dialog box, on the System tab, with Storage Method of 32-bit Numerical Data. For details, refer to
Chapter 4 “3.1 System Tab” on page 4-26.