IDEC High Performance Series User Manual

Page 1396

Advertising
background image

6 HG2S

34-80

WindO/I-NV2 User’s Manual

Performance Specifications

EMC Specifications

*1 Not a guarantee in all usage environments with oil materials.

Color

Monochrome

Display

LCD Type

STN color LCD

STN monochrome LCD

Display Colors

256 Colors

2 Colors

Effective Display
Area [mm]

118.2(W) x 89.4(H) [mm]

Display Resolution

320 (W) x 240 (H) pixels

View angle

Left / Right : 50°,
Top : 45°, Bottom : 35°

Left / Right : 30°,
Top : 20°, Bottom : 30°

Brightness of LCD
only

250 [cd/m

2

]

200 [cd/m

2

]

Contrast
Adjustment

Can be adjusted from the front touch panel

Backlight

Cold-cathode tube

Cold-cathode tube

Backlight Life

40000 hours
(The backlight life refers to the time until
the surface brightness reduces to a half
after using continuously at room
temperatures).

25000 hours
(The backlight life refers to the time until
the surface brightness reduces to a half
after using continuously at room
temperatures).

Touch switch

Switch Type

Digital Resistive Film

Operating Force

0.2 to 0.8 N

Composition

12 × 16
(12 x 10 for the CC SWITCH type)

Life

1,000,000 operations

CC SWITCH

Switch Type

Digital Resistive Film

Operating Force

2.5 to 5.0 N

Quantity
(per screen)

6 x two columns (total: 12) (right and left)

Life

1,000,000 operations

User Memory

2MB

Backup Data

Calendar, Log Data, Keep Internal relay/resister
(Maintenance period: 1 month at 25°C)

Buzzer output

Single tone

Installation structure

Hand-held type

Degree of Protection

CC SWITCH type
TYPE 1, IP20 (housing: IP65) (excluding D-sub connector part)
Touch switch type
TYPE 4, 4X and IP65
TYPE 13

*1

(excluding D-sub connector part)

Weight (approx.)

1.2kg (excluding cable)

Radiated Emission

Class A : 10m
40dBµV/m quasi-peak (30M to 230MHz)
47dBµV/m quasi-peak (230M to 1GHz)

Electrostatic Discharge

Contact : ±6kV
Air : ±8kV

Electromagnetic Field

10V/m (80 to 1000 MHz)
3V/m (1.4 to 2.0 GHz)
1V/m (2.0 to 2.7 GHz)
80% AM (1kHz)

Fast Transient Burst

Power : ±2kV
Communication cable : ±1kV

Surge Immunity

±500V (between +24V-0V)
±500V (between +24V-FE, 0V-FE)

Conducted Radio
Frequency Immunity

3V (Power, Communication cable)
(150kHz to 80MHz)
80% AM (1kHz)

Advertising
This manual is related to the following products: