6 usb autorun function security, Execution privileges by security groups, Usb autorun function security -39 – IDEC High Performance Series User Manual

Page 1283

Advertising
background image

WindO/I-NV2 User’s Manual

30-39

2 USB Flash Drives

30

External Memory Devices

2.6 USB Autorun Function Security

If security has been enabled for the MICRO/I project, MICRO/I displays a password entry dialog box when the USB
Autorun function runs.

Select the user name from the security group that has command execution permissions, enter the password, and
press ENT.

Execution privileges by security groups

The commands that can be executed differ depending on the security group.

Example 1: If these two commands are used in the USB Autorun definition file (hgauto.ini).
Downloading a project file
Copying files (SD memory card to USB flash drive)
The types of user accounts required to execute these commands is given below.

Example 2: If the USB Autorun definition file (hgauto.ini) only contains the file copy command (SD

memory card -> USB flash drive)

A user account from the Administrator, Operator, or Reader security group is required.

Enter the appropriate password
for Data Transfer Function

CAN

User

Up Down

A

B

C

D

E

F

G

H

I

J

K

L

CLR

M

N

O

P

Q

R

S

T

U

V

W

X

ENT

Y

Z

0

1

2

3

4

5

6

7

8

9

Password

Command

Security Group

Administrator

Operator

Reader

Downloading a project file

YES

NO

NO

Uploading a project file

YES

NO

NO

Downloading a PLC program file

YES

NO

NO

Uploading a PLC program file

YES

NO

NO

Copying files (USB flash drive to SD memory card)

YES

YES

NO

Copying files (SD memory card to USB flash drive)

YES

YES

YES

Downloading a project file:

Administrator

File copying (SD memory card to USB flash drive):

Administrator, Operator, or Reader

Pressing the Run All button:

Administrator

The password for the command with the highest security level listed in the USB Autorun definition file
(hgauto.ini) must be entered to execute all commands by pressing the Run All button. In the example
above, a user account from the Administrator security group is required.

If operator presses CAN instead of entering a password, no commands are executed and the menu screen
closes. To re-execute the USB Autorun function, insert the USB flash drive again.