5.8 Wiring

Power Supply Terminal

• Pin assignment is shown in the following table.

• Use applicable cables for wiring and recommended ferrules (made by JST) as follows.

Grounding Cautions

If you decide to use a single power supply for the HG3/4F with more than one external device, take extra precautions.
Some external devices may produce electrical noise and short circuit the entire system setup, therefore, damaging the
communication circuit of the HG3/4F and non-isolated Communication Device (i.e. PLC).
To prevent such damage, choose a proper solution depending on your system setup.

• Use a separate earth ground from the external noise source device.
• The wire for grounding should be thick and short in order to direct the noise from the noise source device to the

earth ground.

• Use a separate power supply from the external noise source device.
• Insert an isolator on the communication line of the HG3/4F and the non-isolated communication device (i.e. PLC) to

prevent damage.

Cautions for using the HG3/4F connected to a personal computer

When connecting the HG3/4F to a personal computer via the Serial Interface, the HG3/4F or the personal computer
may break down depending on the conditions of the personal computer. Make sure of the following cautions, in order
to prevent an accident.

• If the personal computer has a 3-pin power plug or power plug with a ground lead type. make sure to use a plug

socket including a ground input electrode or ground the earth lead, respectively.

• If the personal computer has a 2-pin power plug without ground lead, follow the procedure below when connect

the HG3/4F to the personal computer.
(1) Pull out the power plug of the personal computer from the AC outlet.
(2) Connect the HG3/4F to the personal computer.
(3) Insert the power plug of the personal computer into the AC outlet.

CAUTION

• Turn off the power supply before wiring.
• Make the wiring as short as possible and run all wires as far away as possible from high-voltage

and large-current cables. Follow all the procedures and precautions when wiring the HG3/4F.

• Separate the HG3/4F power supply wiring from the power lines of I/O devices and motor

equipment.

• Ground the functional earth terminal to make sure of correct operation.

+

Power supply 24V DC (+24V)

-

Power supply 0V (0V)

Functional Earth (FE)

Applicable cable

AWG14 to AWG18

Recommended
Pressure Terminal

V1.25(RAV1.25-4), V2-P4 Equivalent

Tightening Torque

1.0 to 1.3 N·m