3 operating modes, Operating modes -4, 3operating modes – IDEC High Performance Series User Manual

Page 28

Advertising
background image

3 Operating Modes

1-4

WindO/I-NV2 User’s Manual

The MICRO/I includes multiple modes, so you switch between modes as and when necessary. These modes are called
operating modes. The functions and the operations and conditions for switching are as follows.

3

Operating Modes

Mode

Functions

Conditions required for

switching to the mode

Run Mode

This is the mode at the time of executing project
data. The created screen is displayed.

• Turn ON the power to the MICRO/I.
• Press [Run] on the Top Page of system

mode or on the System Menu.

• The download of the project data is

completed.

System Mode

Perform initial settings, clock settings, self-diagnosis,
etc. for the MICRO/I.

• Display the Maintenance Screen with the

following methods and press [System
Mode].

HG2G-S/-5S/-5F, HG3G/4G, HG1F:

Press the upper-left
corner of the MICRO/I
screen for three
seconds or more.

HG2F/2S/3F/4F:

Simultaneously press
the upper-left and
upper-right corners of
the MICRO/I screen.

• Using the screen switching button, multi-

buttons, screen switch or multi commands,
switch to the System Mode.

• All data is cleared using WindO/I-NV2.
• Write the System Area 1 Display screen

number (address+0) to FFFFh.

Monitor Mode

Monitor Mode is used for monitoring values of
devices using WindO/I-NV2.
In this mode, the following message blinks on the
bottom-left of the MICRO/I screen.

HG2G-S/-5S/-5F, HG3G/4G: Monitor Mode
HG1F/2F/2S/3F/4F:

Debug Mode

On the WindO/I-NV2 Online tab, in the
Monitor group, click Start Monitor.

Simulation Mode

This mode simulates the external device's device
values.
In this mode, the message "Simulation Mode" blinks
on the bottom-left of the MICRO/I screen.

• Press the following buttons in System Mode.

HG2G-S/-5S/-5F, HG3G/4G:

[Simulate] on the Top
Page

HG1F/2F/2S/3F/4F:On the System Menu,

[Debug], [Simulation],
[Start]

• While monitoring in WindO/I-NV2, on the

[Online] tab, in the [Monitors] group, click
[Start Simulation].

Data Transfer

Transferring data between a computer and the
MICRO/I.

• Download project data.
• Upload project data.

• When switched to System Mode, operation of the MICRO/I stops.
• To display the Maintenance Screen, the Enable Maintenance check box from the System Settings

tab of the Project Settings dialog box must be checked.

For details about Maintenance Mode, refer to Chapter 33 “1 Maintenance Screen” on page 33-1.

Advertising
This manual is related to the following products: