IDEC High Performance Series User Manual

Page 172

Advertising
background image

5 User Communication

3-70

WindO/I-NV2 User’s Manual

Receive command: Command Settings dialog box settings

Operation for receive command

1

When data transmission of the transmission command is completed, the value of LM101 changes to 1, and since the
same device is specified for the trigger condition user communication becomes ready for receiving.

2

Data is transmitted from the external device and the transmitted data is received and processed.
The receive data is as follows.

Since a value of 100 is written to LDR100 at the time of transmission, the data is stored in device LDR220, which
corresponds to an offset of +100 from LDR120.

• When data reception is successfully completed, the Completed Device LM102 changes to 1.
• When the value of each bit of address+0 of Status Device LDR130 is 0, reception is completed without an error.

Item

Setting

Comment

RXD command

Command Type

Receive

Completed Device

LM102

Not Clear Completed Device
automatically

No

Status Device

LDR130

Receiving Time Out

0 (No Receive Time Out)

Trigger Condition

While ON, Device: LM101

Command
Data Settings dialog box settings

Constant
(Hexadecimal)

'02'

Constant
(Character)

"D"

Device

Conversion Type: ASCII (HEX) to Binary,
Number of bytes: 4, Words: 1
Device: LDR120, Reference Device: LDR100

Constant
(Hexadecimal)

'0D'

D

(44h)

3

(33h)

4

(34h)

1

(31h)

STX

(02h)

2

(32h)

CR

(0Dh)

Receive data:

Constant

(HEX)

Constant

(Character)

Device

Command settings:

Constant

(HEX)

0000

LDR120:

0000

LDR121:

1234h

LDR220:

Value of Device

LDR230=100

Advertising
This manual is related to the following products: