IDEC High Performance Series User Manual

Page 1280

Advertising
background image

2 USB Flash Drives

30-36

WindO/I-NV2 User’s Manual

Notes on comments

To add comments to the USB Autorun definition file, use a semicolon (;).
All text after the semicolon (;) and up to the line feed will be treated as a non-executable comments.

Restrictions

• The maximum number of characters per line is 512 single-byte characters including line feed codes.

All the text on the line will be ignored if there are more than 512 single-byte characters on the line.

• Each item must be described as a single line. If a line feed occurs before the end of the description, all characters

after the line feed are ignored.

• The maximum size of the USB Autorun definition file (hgauto.ini) is 512 KB. The file cannot be used if it exceeds

this limit.

• Only line feed codes of the format generally supported by Windows (CR+LF) are supported. If any other format is

used, the USB Autorun definition file (hgauto.ini) will fail to run properly.

Sample definition file and explanation

Sample definition

; sample hgauto.ini

(1)

[AUTORUN]
item = 5

; number of items

button_command = Enable

; enable individual command buttons

button_runall = Enable

: enable the "Run All" button.

language =English

; use English

(2)

[COMMAND_1]
command = PRO_DOWNLOAD

; download the project file

src_path = "B:

\

HG3G_DEMO_1.ZNV"

; source path

title = "Production line A - replace display program"

; button label

(3)

[COMMAND_2]
command = FILE_COPY

; copy a file

src_path = "B:

\

Error.wav"

; source path

dst_path = "A:

\

HGDATA01

\

SOUND"

; destination path

title = "Replace sound data"

; button label

(4)

[COMMAND_3]
command = LDR_DOWNLOAD

; download PLC program file

src_path = "B:

\

LDRDATA

\

LDR_PROGRAM.ZLD"

; source path

dst_port = COM1

; destination port number

dst_net_no = 0

; destination station number

title = "Production line A - replace PLC program"

; button label

(5)

[COMMAND_4]
command = PRO_UPLOAD

; upload a project file

dst_path = "B:

\

Uploaded_Project"

; destination path

title = "Copy display program to USB flash drive"

; button label

(6)

[COMMAND_5]
command = LDR_UPLOAD

; Upload a PLC program file

dst_path = "B:

\

Uploaded_Program"

; destnation path

src_port = COM1

; source port number

src_net_no = 0

; source station number

title = "Copy PLC program to USB flash drive"

; button label

(7)

[COMMENT]
comment = " Press the command to execute."

; Message shown at bottom of screen.

Advertising