8 wiring, Power supply terminal, Grounding cautions – IDEC High Performance Series User Manual

Page 1359: Wiring -43, Micro/ i specif ication s, Caution

Advertising
background image

WindO/I-NV2 User’s Manual

34-43

3 HG1F

34

MICRO/

I Specif

ication

s

3.8 Wiring

Power Supply Terminal

• Pin assignment is shown in the following table.

• Use applicable cables for wiring and recommended ferrules (made by Phoenix Contact) as follows.

Grounding Cautions

If you decide to use a single power supply for the HG1F with more than one external device, take extra precautions.
Some external devices may produce electrical noise and short circuit the entire system setup, therefore, damaging the
communication circuit of the HG1F and non-isolated Communication Device (i.e. PLC).
To prevent such damage, choose a proper solution depending on your system setup.

• Use a separate earth ground from the external noise source device.

• The wire for grounding should be thick and short in order to direct the noise from the noise source device to the

earth ground.

• Use a separate power supply from the external noise source device.

• Insert an isolator on the communication line of the HG1F and the non-isolated communication device (i.e. PLC) to

prevent damage.

Cautions for using the HG1F connected to a personal computer

When connecting the HG1F to a personal computer via the Serial Interface the HG1F or the personal computer may
break down depending on the conditions of the personal computer. Make sure of the following cautions, in order to
prevent an accident.

• If the personal computer has a 3-pin power plug or power plug with a ground lead type. make sure to use a plug

socket including a ground input electrode or ground the earth lead, respectively.

• If the personal computer has a 2-pin power plug without ground lead, follow the procedure below when connect

the HG1F to the personal computer.

(1) Pull out the power plug of the personal computer from the AC outlet.
(2) Connect the HG1F to the personal computer.
(3) Insert the power plug of the personal computer into the AC outlet.

CAUTION

• Turn off the power supply before wiring.
• Make the wiring as short as possible and run all wires as far away as possible from high-voltage

and large-current cables. Follow all the procedures and precautions when wiring the HG1F.

• Separate the HG1F power supply wiring from the power lines of I/O devices and motor equipment.
• Ground the functional earth terminal to make sure of correct operation.

+

Power supply 24V DC (+24V)

-

Power supply 0V (0V)

Functional Earth (FE)

Applicable cable

AWG18 to AWG22

Recommended
Pressure Terminal

AI 0.34-6 TQ
AI 0.5-8 WH
AI 0.75-8 GY
AI 1-8 RD
AI-TWIN 2×0.5-8 WH (TWIN Pressure Terminal)
(Phoenix Contact)

Tightening Torque

0.5 to 0.6 N•m

Advertising
This manual is related to the following products: