Sigma II User’s Manual

Chapter 5: Parameter Settings and Functions

5 - 20

Example of I/O Signal Generation Timing

Note: 1. In order for the input pulse to register, the interval from the time the servo ON signal is turned

ON until a reference pulse is entered must be a minimum of 40ms.

2. The error counter clear signal must be on for at least 20

μs.

Reference Pulse Input Signal Timing

Reference Pulse Form

Electrical Specifications

Sign + pulse train input

(SIGN + PULS signal)

Maximum reference

frequency: 500kpps

(200kpps open-collector

output)

t1, t2

≤ 0.1µs

t3, t7

≤ 0.1µs

t4, t5, t6 > 3µs

τ ≥ 1.0µs

(

τ/T) × 100 ≤

50%

Sign (SIGN)

H = Forward reference

L = Reverse reference

CW pulse and CCW

pulse

Maximum reference

frequency: 500kpps

(200kpps open-collector

output)

t1, t2

≤ 0.1µs

t3 > 3µs

τ ≥ 1.0µs

(

τ/T) × 100 ≤

50%

Two-phase pulse train

with 90

° phase differential

(A phase + B phase)

Maximum reference

frequency

×

1: 500kpps

(200kpps open-collector

output)

×

2: 400kpps

×

4: 200kpps

t1, t2

≤ 0.1µs

τ ≥ 1.0µs

(τ/T) × 100 =

50%

Parameter Pn200.0 is

used to switch the

input pulse multiplier

mode.

Servo ON

Baseblock

Sign+pulse

train

Release

PG pulse

CN1-1

1

CN1-

7

PAO

PBO

t6

t1

≤ 30ms

t2

≤ 6ms

(when parameter

Pn506 is set to 0)

t3

≥ 40ms

t4, t5, t6

≤ 2ms

t

7 ≥ 20ms

CN1-11

CN1-7

t7

t2

t1

t3

t4

t5

t6

T

τ

Forward

reference

Reverse

reference

SIGN

PULS

Forward

reference

Reverse

reference

t2

t1

t3

T

τ

CCW

CW

Forward

reference

Reverse

reference

t2

t1

T

τ

A phase

B phase

B phase leads

A phase by 90°

B phase lags

A phase by 90°