A.10, Display and outputs, Status and remedy for alarm – Yaskawa Sigma II Series Servo System User Manual

Page 396

Advertising
background image

Sigma II User’s Manual

Chapter 9: Inspection, Maintenance, and Troubleshooting

9 - 8

A.10

A.10: Overcurrent or Heat Sink Overheated

Display and Outputs

Note:

OFF:

Output transistor is OFF (alarm state).

ON:

Output transistor is ON.

Status and Remedy for Alarm

Note:

Problems E to H can occur in a servo amplifier with a capacity of
1.5 to 5kW, and all 400V models.

Alarm Outputs

Alarm Code Output

ALM Output

ALO1

ALO2

ALO3

ON

OFF

OFF

OFF

Cause of the Problem

Solution

A

Shorted wiring between servo

amplifier and servomotor.

Check and correct wiring.

B

Shorted servomotor U, V, or W

phase.

Replace servomotor.

C

• Defective circuit board (1PWB)

.

• Defective power transistor.

Replace servo amplifier.

D

Defective current feedback circuit,

power transistor, DB circuit, or cir-

cuit board.

Replace servo amplifier.

E

Ambient temperature of the servo

amplifier greater than 55°C.

Alter conditions so that the ambi-

ent temperature is below 55°C.

F

Inadequate air flow around the

heat sink.

Providing sufficient space as

specified.

G

Fan stopped.

Replace servo amplifier.

H

Servo amplifier is operating under

an overload.

Reduce load.

When Servo ON (S-ON)

At power ON.

During servomotor

operation.

ssignal is turned ON.

A, B, D,

C

C, D

E, F, G