Using the built-in panel operator – Yaskawa Sigma II Series Servo System User Manual
Page 330

Sigma II User’s Manual
Chapter 7: Using the Digital Operator
7 - 56
Using the Built-in Panel Operator
1.
Press the MODE/SET key to select the auxiliary function mode.
2.
Select the parameter Fn014.
Press the Left Arrow or Right Arrow key to select the digit.
Press the Up Arrow or Down Arrow key to change the value.
3.
Press the DATA/SHIFT key for a minimum of one second, and the display will
be as shown below.
4.
Press the MODE/SET key, and the display will be as shown below. The
parameters will be initialized.
5.
Press the DATA/SHIFT key for a minimum of one second to return to the
auxiliary function mode display.
This completes the initialization of parameter settings.
SGDM-
MODE/SET
DATA/
CHARGE
POWER
SERVOPACK
200V
YASKAWA
Flashing for
one second
Flashing during
initialization
End