Sigma II User’s Manual

Chapter 5: Parameter Settings and Functions

5-137

5.10.4 Reference Pulse Input Multiplication Range Switching Function

The position reference pulse input multiplication setting range can be switched between "×1" and "×1 to

×99."

Set Pn218.0 = 1 to enable this function, and set the multiplication in Pn217.

To change the reference pulse multiplication, the position reference pulse must be set to 0. Otherwise, the

operation cannot be guaranteed.

This function is valid only for "reference pulse" and disabled for the reference pulse set from the option

board in the configuration "SGDH servomotor and option board.î

×

1

×

n

(n

=Pn217

×

1

Reference pulse

input switching

(/PSEL)

Enable

Disable

Reference pulse

input switcing

(/PSELA)

Enable

Internal processing

4ms or less

4ms or less

Disable

Fig.1 Timing Chart for Reference Pulse Input Multiplication Change

Related Parameters

Parameter

Note:

After changing the setting, turn OFF the control power supply and turn ON again to enable the new setting.

Note:

The change of setting value is enabled in online mode.

Parameter

No.

Digit

Place

Name

Setting

Contents

Factory

Setting

Pn218

0

Reference pulse input multi-
plication range switching func-
tion

0

Disabled

0: Disabled

1

Enabled

Parameter

No.

Name

Unit

Setting Range

Factory

Setting

Pn217

Reference Pulse Input Multiplica-

tion

×

1

×

1 to

×

99

1