Sigma II User’s Manual

Chapter 5: Parameter Settings and Functions

5-76

5.5.4

Speed Coincidence Output (/V-CMP)

The basic use and wiring procedures for the speed coincidence (/V-CMP) output

signal (photocoupler output signal), used to indicate a match with the speed

reference, are described below. The host controller uses the signal as an interlock.

This signal is output when the actual motor speed during speed control is the same as
the speed reference input.

The following parameter setting is used to change the CN1 connector terminal that
outputs the /V-CMP signal.

The parameter is default set so the /V-CMP signal is output between CN1-25 and 26.
See 5.3.4 Output Circuit Signal Allocation for more details on parameter Pn50E.

Output /V-CMP CN1-25

Speed Coincidence Output

Signal

Speed Control

/V-CMP

State

Status

Result

ON

Circuit between CN1-25 and 26 is

closed, and CN1-25 is at low level.

Speed coincides. (Speed error is below

the setting).

OFF

Circuit between CN1-25 and 26 is

open, and CN1-25 is at high level.

Speed does not coincide. (Speed error

is above the setting).

Parameter

Signal

Setting

(rpm)

Description

Pn50E

Output Signal Selections 1

Default Setting: 3211

Position Control

+24V

0V

Servo amplifier

I/O power supply

Photocoupler output levels per output node:
• Maximum operating voltage: 30V

DC

• Maximum output current: 50mA

DC

CN1-25 /V-CMP+

CN1-26 /V-CMP-

Motor

speed

Reference speed

/V-CMP is output in this range.

Pn503