Sigma II User’s Manual

Chapter 3: Wiring

3 - 20

Output Signals

Note 1. Pin numbers in parenthesis () indicate signal grounds.

2. The functions allocated to /TGON, /S-RDY, and /V-CMP (/COIN) can be changed via

parameters. Functions /CLT, /VCT, /BK, /WARN, and /NEAR signals can also be changed. (See
5.3.4 Output Circuit Signal Allocation ).

Signal Name

Pin

Number

Function

Reference

Common

ALM+

ALM-

31

32

Servo alarm: Turns OFF when an error is detected.

5.5.1

/TGON+

/TGON-

27

28

Detection during servomotor rotation: detects whether the servomotor is

rotating at a speed higher than the motor speed setting. Motor speed

detection can be set via parameter.

5.5.5

/S-RDY+

/S-RDY-

9

30

Servo ready: ON if there is no servo alarm when the control/main circuit

power supply is turned ON.

5.5.6

PAO

/PAO

PBO

/PBO

PCO

/PCO

33 (1)

34

35

36

19

20

A phase signal

B phase signal

C phase signal

Converted two-phase pulse (A and B phase) encoder

output signal and origin pulse (C phase) signal: RS-422

or the equivalent.

5.2.3

PSO

/PSO

48

49

S phase signal

With an absolute encoder: outputs serial data

corresponding to the number of revolutions (RS-422 or

equivalent).

ALO1

ALO2

ALO3

37

38

39 (1)

Alarm code output: Outputs 3-bit alarm codes.

Open-collector: 30V and 20mA rating maximum.

5.5.1

FG

Shell

Connected to frame ground if the shield wire of the I/O signal cable is

connected to the connector shell.

Speed

/V-CMP+

/V-CMP-

25

26

Speed coincidence (output in Speed Control Mode): detects whether the

motor speed is within the setting range and if it matches the reference

speed value.

5.5.4

Position /COIN+

/COIN-

25

26

Positioning completed (output in Position Control Mode): turns ON when

the number of error pulses reaches the value set. The setting is the

number of error pulses set in reference units (input pulse units defined by

the electronic gear).

5.5.3

Not used.

16

17

23

24

50

These terminals are not used.

Do not connect relays to these terminals.