Sigma II User’s Manual

Chapter 5: Parameter Settings and Functions

5-69

Brake ON Timing

If the equipment moves slightly due to gravity when the brake is applied, set the

following parameter to adjust brake ON timing.

This parameter is used to set the output time from the brake control signal /BK until
the servo OFF operation (servomotor output stop) when a servomotor with a brake is
used.

With the standard setting, the servo is turned OFF when the /BK signal (brake

operation) is active. The equipment may move slightly due to gravity depending on
equipment configuration and brake characteristics. If this happens, use this

parameter to delay servo OFF timing.

This setting sets the brake ON timing when the servomotor is stopped. Use Pn507
and 508 for brake ON timing during operation.

Note: The servomotor will turn OFF immediately if an alarm occurs. The equipment may move due to

gravity in the time it takes for the brake to operate.

Parameter

Signal

Setting
(10ms)

Description

Pn506

Brake Reference Servo OFF

Delay Time

Setting Range: 0 to 50

Default Setting: 0

Speed/Torque Control,

Position Control

/S-ON input

(CN1-40)

/BK output

Servo ON/OFF

operation

(Servomotor

ON/OFF status)

Release brake

Servo ON

Servomotor

ON

Hold with brake

Servo OFF

Servomotor OFF

Servo OFF

time delay