External mounted db contactor specification – Yaskawa Sigma II Series Servo System User Manual

Page 215

Advertising
background image

Sigma II User’s Manual

Chapter 5: Parameter Settings and Functions

5-129

External Mounted DB Contactor Specification

Note: If the customer uses a contactor other than the one specified above, choose a contactor that is closest

to the one specified above. Most importantly choose a contactor that has a coil resistance value higher
than the one listed above.

Install the Main Circuit Surge Absorption Unit, and Coil Surge Absorption Unit
(Chosen by the Customer) to the Contactor as illustrated below.

Make sure that the contactor can withstand the surge current as shown below.

Model

SC-4-1/G DC24V

Maker

Fuji Electric Co. , Ltd.

Standard Coil Voltage

DC24V

Coil Resistance

90W ±10%

Operating
Time

Coil ON
contactor ON

44~48mSEC

Coil OFF
contactor OFF

22~28mSEC

Rated Current

32A

Rated Using Current (Resistor Load (AC1))
380-440V

32A

Main Circuit Surge Absorption Unit
(Fuji Electric Co., Ltd.)

SZ-ZM1 (Radial Lead)
or
SZ-ZM2 (Axial Lead)

Coil Surge Absorb Unit
(Fuji Electric Co., Ltd.)

SZ-Z4

Main Circuit Surge Absorption Unit

DB Resistor

Coil Surge Absorption Unit

DB Contactor

Servopack

DU DV DW

DBON

DB24