A.73, Display and outputs, Status and remedy for alarm – Yaskawa Sigma II Series Servo System User Manual

Page 404

Advertising
background image

Sigma II User’s Manual

Chapter 9: Inspection, Maintenance, and Troubleshooting

9 - 16

A.73

A.73: Dynamic Brake Overload

Display and Outputs

Note:

OFF:

Output transistor is OFF (alarm state).

ON:

Output transistor is ON.

Status and Remedy for Alarm

Alarm Outputs

Alarm Code Output

ALM Output

ALO1

ALO2

ALO3

ON

ON

ON

OFF

Cause of the Problem

Solution

A

The product of the square of rotational motor

speed, the combined inertia of the motor,

and load (rotation energy) exceeds the

capacity of the dynamic brake resistor built

into servo amplifier.

• Reduce the rotational speed.

• Decrease the load inertia.

• Minimize use of the dynamic brake.

B

Defective circuit board (1PWB).

Replace servo amplifier.

When the Servo OFF (/S-ON)

signal is turned ON.

At power ON.