A.7a, Display and outputs, Status and remedy for alarm – Yaskawa Sigma II Series Servo System User Manual

Page 406

Advertising
background image

Sigma II User’s Manual

Chapter 9: Inspection, Maintenance, and Troubleshooting

9 - 18

A.7A

A.7A: Heat Sink Overheated
Heat sink temperature exceeds 100°C.

Display and Outputs

Note:

OFF:

Output transistor is OFF (alarm state).

ON:

Output transistor is ON.

Status and Remedy for Alarm

Note:

Larger servo amplifiers (1.5kW., or larger) will display alarm A.10 if the
heat sink overheats.

Alarm Outputs

Alarm Code Output

ALM Output

ALO1

ALO2

ALO3

ON

ON

ON

OFF

Cause of the Problem

Solution

A

The ambient temperature of the

servo amplifier exceeds 55°C.

Alter conditions so that the ambi-

ent temperature goes below

55°C.

B

Inadequate air flow around the

heat sink .

Provide sufficient space as speci-

fied.

C

Fan stopped.

Replace servo amplifier.

D

Servo amplifier is operating under

overload.

Reduce load.

E

Defective servo amplifier.

Replace servo amplifier.

During servomotor

operation.

When control power

is turned ON.

E

A, B

C, D