Sigma II User’s Manual

Chapter 5: Parameter Settings and Functions

5-75

The following parameter is used to change the CN1 connector terminal that outputs
the /COIN signal.

The parameter is factory set so the /COIN signal is output between CN1-25 and 26.
See 5.3.4 Output Circuit Signal Allocation for more details on parameter Pn50E.
The following parameter is used to set the number of error pulses and to adjust the
output timing of the positioning completed signal.

Note: *reference units for this parameter are the number of input pulses as defined using the electronic gear

function

.

This parameter is used to set output timing for the positioning completed signal

(/COIN) when the position reference pulse is input and servomotor operation is

completed.
Set the number of error pulses in reference units.
Too large a value set at this parameter may output only a small error during

low-speed operation that will cause the /COIN signal to be output continuously.
The positioning completed width setting has no effect on final positioning accuracy.

Note: /COIN is a position control signal.

With the default setting, this signal is used for the speed coincidence output /V-CMP for speed

control, and it is always ON for torque control.

Parameter

Signal

Setting

(rpm)

Description

Pn50E

Output Signal Selection 1

Default Setting: 3211

Position Control

Parameter

Signal

Setting

(reference units*)

Description

Pn500

Positioning Completed Width

Setting Range: 0 to 250

Default Setting: 7

Position Control