Using the built-in panel operator – Yaskawa Sigma II Series Servo System User Manual
Page 320

Sigma II User’s Manual
Chapter 7: Using the Digital Operator
7 - 46
This completes the manual zero adjustment of the analog monitor output.
Using the Built-in Panel Operator
1.
Press the MODE/SET key to select the auxiliary function mode.
2.
Press the Up Arrow or Down Arrow key to select the parameter Fn00C.
3.
Press the DATA/SHIFT key for a minimum of one second, and the display will
be as shown below.
4.
Press the MODE/SET key. Each time the MODE/SET key is pressed, the
monitor output will toggle between the displays for the two channels shown
below.
5.
Press the DATA/SHIFT key for less than one second, and the analog monitor
gain parameter will be displayed. Pressing the DATA/SHIFT key again for less
than one second will return to the display shown in the above steps 3 or 4.
6.
Press the Up Arrow or Down Arrow key to perform zero adjustment of the
analog monitor output.
7.
When zero adjustment has been completed for the two channels, press the
DATA/SHIFT
key for a minimum of one second to return to the auxiliary
function mode display.
This completes the manual zero adjustment of the analog monitor output.
SGDM-
MODE/SET
DATA/
CHARGE
POWER
SERVOPACK
200V
YASKAWA
MODE/SET Key
Displayed
Alternately
Data Display
DATA/SHIFT Key
Displayed
Alternately
Data Setting Change