Sigma II User’s Manual

Chapter 5: Parameter Settings and Functions

5 - 48

settings.

Setting

The torque limit is set at parameter Pn400.
The default setting at Pn400 is 30. If, for example, the torque limit is ±3V, then
torque is limited to 100% of the rated torque. (A torque value higher than 100%
torque is clamped at 100%.)

When either the P-CL or the N-CL signal is turned ON, the following torque limits
become valid simultaneously.

Input

Signal

Signal Level

Description

Comments

/P-CL

CN1-45 is at “L” level when

ON

Torque is limited at the

forward run side.

Limit value: either Pn404 or

T-REF input, whichever is

smaller.

CN1-45 is at “H” level when

OFF

Torque is not limited at the

forward run side.

Normal Operation

/N-CL

CN1-46 is at “L” level when

ON

Torque is limited at the

reverse run side.

Limit value: either Pn405 or

T-REF input, whichever is

smaller.

CN1-46 is at “H” level when

OFF

Torque is not limited at the

forward run side.

Normal operation.

Parameter

Signal

Setting

(rpm)

Control Mode

Pn400

Torque Reference Input Adjust-

ment Factor

Setting Range: 0 to 100

Default Setting: 30

Speed/Torque Control

Parameter

Signal

Setting

(rpm)

Control Mode

Pn404

Forward Run Side External Torque

Limit

Setting Range: 0 to 800

Default Setting: 100

Speed/Torque Control,

Position Control

Pn405

Reverse Run Side External Torque

Limit

Setting Range: 0 to 800

Default Setting: 100

Speed/Torque Control,

Position Control