5.2.11 Reference Pulse Inhibit Function (/INHIBIT)

This function inhibits the servo amplifier from counting input reference pulses

during position control. The servomotor remains locked (clamped) while the

function is in use. The /P-CON(/INHIBIT) signal is used to enable or disable the
function.

Using Reference Pulse Inhibit Function (/INHIBIT)

To use the inhibit function, set the parameter as shown below.

The following settings enable the inhibit function.

Note: Parentheses ( ) around an /INHIBIT signal indicate that a signal has been allocated to the input circuit.

See 5.3.3 Input Circuit Signal Allocation for more details.

Parameter

Signal

Setting

(rpm)

Control Mode

Pn000.1

Control Method Selection

Default Setting: 0

Position Control

Pn000.1 Setting

Description

1

Enables the inhibit function.

Always counts reference pulses.

B

Enables the inhibit function. The /P-CON (/INHIBIT) signal is used to

enable or disable the inhibit function.

/P-CON (/INHIBIT)

Description

OFF

Counts reference pulses.

ON

Prohibits the servo amplifier from

counting reference pulses.

The servomotor remains locked.

Pn000.1

Error

counter

Reference

pulse

1

B

OFF

O

N

+

-

Feedback pulse

Servo Amplifier

P-CON (INHIBIT)

P-CON

(INHIBIT)