A.e7, Display and outputs, Status and remedy for alarm – Yaskawa Sigma II Series Servo System User Manual

Page 421

Advertising
background image

Sigma II User’s Manual

Chapter 9: Inspection, Maintenance, and Troubleshooting

9 - 33

A.E7

A.E7: Option Unit Detection Error
A.E7 occurs the first time the SGDH amplifier is used after disconnecting an option
unit. This alarm cannot be cleared with an alarm reset; instead, clear it with function
Fn014.

Display and Outputs

Note:

OFF:

Output transistor is OFF (alarm state).

ON:

Output transistor is ON.

Status and Remedy for Alarm

Alarm Outputs

Alarm Code Output

ALM Output

ALO1

ALO2

ALO3

ON

ON

OFF

OFF

Cause of the Problem

Solution

A

The SGDH amplifier is used

immediately after disconnection of

an option unit without clearing the

unit detector.

To use the SGDH amplifier after disconnecting

the option unit, execute Fn014 (option unit

detection result clear), in the auxiliary function

mode, and then cycle the power.

B

Option unit connection is defective.

Check and correct the connection.

C

Option unit is defective.

Replace the option unit.

D

Servo amplifier

Replace the servo amplifier.

When the control power is
turned ON after disconnecting

When the control power

is turned ON with an option

an option unit

unit connected.

B, C, D

A