4 setting stop functions, 1 adjusting offset, 4 setting stop functions - 62 – Yaskawa Sigma II Series Servo System User Manual

Page 148: 1 adjusting offset - 62, 4 setting stop functions -62, Adjusting offset -62, Reference offset adjustment

Advertising
background image

Sigma II User’s Manual

Chapter 5: Parameter Settings and Functions

5-62

5.4 Setting Stop Functions

This section describes the procedure used to stop the servo amplifier properly.

5.4.1

Adjusting Offset

When the Servomotor Will Not Stop

The servomotor may rotate at very low speed and not stop even when 0V is specified
as the reference voltage for servo amplifier speed and torque control (analog

reference). This happens when the reference voltage from the host controller or
external circuit is slightly offset (in mV units). The servomotor will stop if this

offset is properly adjusted to 0V.

Reference Offset Adjustment

The following methods can be used to adjust the reference offset to 0V.

Note: Use manual rather than automatic adjustment if a position control loop is formed in the host con-

troller.

See the following sections in Chapter 7 Using the Digital Operator for more details
on adjustment procedures.

Adjustment Method

Result

Automatic Adjustment of Reference Offset

The reference offset is automatically adjusted to 0V.

Manual Adjustment of Reference Offset

The reference offset can be set to a specified value.

Adjustment Method

Reference Source

Automatic Adjustment of Reference

Offset

7.2.3 Automatic Adjustment of the Speed and Torque Reference Offset

Manual Adjustment of Reference

Offset

7.2.4 Manual Adjustment of the Speed and Torque Reference Offset

Offset

Offset adjustment

Reference

voltage

Reference

voltage

Reference

speed or

torque

Reference

speed or

torque

Offset

corrected by

the servo

amplifier