Sigma II User’s Manual

Chapter 6: Servo Adjustment

6 - 5

6.1.4

Adjusting Offset

The servo system does not operate smoothly if reference voltage from the host
controller or external equipment has a reference offset value close to 0V. In that
case, adjust the reference offset value to 0V.

Reference Voltage Offset from Host Controller or External Circuitry

Reference Offset Adjustment

The following two methods are provided to reset the reference offset value to 0V.

Reference offset automatic adjustment

Reference offset manual adjustment

If a position loop is formed in the host controller, be sure to make a manual offset
adjustment and do not make automatic reference offset adjustment.

Refer to the following sections in Chapter 7: Using the Digital Operator for a
detailed description of reference offset adjustment.

6.1.5

Setting the Torque Reference Filter Time Constant

If there is machine vibration which may be caused by the servodrive, try adjusting
the filter time constant in Pn401. This may stop the vibration.

The above constant is the filter time constant of the torque reference to be set in the
servo amplifier. The smaller the value, the faster the speed control response will be.
There is, however, a limit, depending on machine conditions.

Adjustment Method

Detailed Description

Automatic

7.2.3 Automatic Adjustment of the Speed and Torque Reference Offset

Manual

7.2.4 Manual Adjustment of the Speed and Torque Reference Offset

Parameter

Signal

Setting

(x 0.01ms)

Application

Pn401

Torque Reference Filter Time

Constant

Setting Range: 0 to 65535

Default Setting: 100

Speed/Torque Control,

Position Control

Offset

Offset adjustment

Reference speed

or reference

torque

Reference

voltage

Reference

voltage

Reference speed

or reference

torque

Make offset

adjustment with the

servo amplifier