Sigma II User’s Manual

Chapter 5: Parameter Settings and Functions

5-119

Installation and Wiring a Noise Filter

Incorrect application of a noise filter significantly reduces its benefits. Follow these
instructions for the best results.

Separate the input lines from the output lines.

Do not put the input and output lines in the same duct or bundle them together.

Isolate the noise filter ground wire from the output lines.

Do not put the noise filter ground wire, output lines and other signal lines in the
same duct or bundle them together.

Filter

Filter

Filter

Filter

Separate these circuits.

BOX

BOX

The ground wire

can be close to

input lines.

Filter