Sigma II User’s Manual

Chapter 9: Inspection, Maintenance, and Troubleshooting

9 - 5

9.2 Troubleshooting

This section describes causes and remedies for problems which generate an alarm display
and for problems which result in no alarm display.

9.2.1

Troubleshooting Problems with Alarm Displays

Problems that occur in the servodrives are displayed on the panel operator as
“A.

” or “CPF

”. Refer to the following sections to identify the cause of an

alarm and the action to be taken.
Contact Yaskawa if the problem has not been solved after following the described
procedures.

Note: “A.- -: Normal Operation”, is not an alarm. Additional information appears on 38.

A.02

A.02: Parameter Breakdown

Display and Outputs

Note:

OFF:

Output transistor is OFF (alarm state).

Status and Remedy for Alarm

Alarm Outputs

Alarm Code Output

ALM Output

ALO1

ALO2

ALO3

OFF

OFF

OFF

OFF

Cause of the Problem

Solution

A

Power turned OFF during param-

eter write. Alarm occurred at next

power ON.

• Initialize parameters using

Fn005 then reenter settings .

• Replace the servo amplifier.

B

Circuit board (1PWB) defective.

Replace the servo amplifier.

At power ON.

A, B