Sigma II User’s Manual

Chapter 5: Parameter Settings and Functions

5-91

If the previous calculation determines that the amount of regenerative power (W

Wk.

)

that can be processed by the built-in resistor is not exceeded, then an external

regenerative resistor is not required.
If the amount of regenerative power that can be processed by the built-in resistor is
exceeded, install an external regenerative resistor for the capacity obtained from the
above calculation.
If the energy consumed by load system loss (in step 2 above) is unknown, then

perform the calculation using E

L

= 0.

When the operation period in regeneration mode is continuous, add the following
items to the above calculation procedure in order to find the required capacity (W)
for the regenerative resistor.

Energy for continuous regeneration mode operation period: E

G

(joules)

Energy consumed by regenerative resistor: E

K

=

E

S

- (E

L

+ E

M

+ E

C

) + E

G

Required capacity of regenerative resistor: W

K

= E

K

/ (0.2

×

T)

Here, E

G

= (2

π

/60) N

MG

×

τ

G

×

t

G

τ

G

: Servomotor’s generated torque [oz-in (N-m)] in continuous regeneration

mode operation period.

N

MG

: Servomotor rotation speed (rpm) for same operation period as above.

t

G

: Same operation period (s) as above.