Sigma II User’s Manual

Chapter 5: Parameter Settings and Functions

5-110

5.8 Special Wiring

This section describes special wiring methods including the one for noise control. In

addition to 5.8.1 Wiring Precautions and 5.8.2 Wiring for Noise Control, refer to other
sections as necessary.

5.8.1

Wiring Precautions

To ensure safe and stable operation, always observe the following wiring

precautions:
1. Always use the following cables for reference input and encoder wiring.

Trim off the excess portion of the cable to minimize the cable length.

2. For a ground wire, use as large a wire as possible: AWG14( 2.0mm

2

) or larger.

At least class-3 ground (100

Ω maximum) is recommended.

Ground to one point only.

If the motor is insulated from the machine, ground the motor directly.

3. Do not bend or apply tension to cables.

The conductor of a signal cable is very thin (0.0079 to 0.012in. (0.2 to 0.3mm)),
handle the cables with care.

4. Use a noise filter to prevent noise interference.

(For details, Refer to 5.8.2 Wiring for Noise Control).

If the equipment is to be used near private houses or may receive noise

interference, install a noise filter on the input side of the power supply line.

Since this servo amplifier is designed as an industrial device, it provides no
mechanism to prevent noise interference.

5. To prevent malfunction due to noise, take the following actions:

Cable Type

Yaskawa

Drawing Number

Maximum Allowable Length

Reference

Input

Twisted pair wires

JZSP-CKI01

118in (3m)

Encoder

Multi-conductor

shielded twisted

pair wire

JZSP-CMP00

SGMAH, SGMPH

787in (20m)

JZSP-CMP02

SGMGH, SGMSH

1969in (50m)