Loaded operation, Connecting the load, Operation using the digital operator – Yaskawa G7 Drive User Manual

Page 104: Loaded operation -15

Advertising
background image

Trial Operation Procedures

4-

15

‹

Loaded Operation

Connect the machine to the motor and then start operation as described for no-load operation (i.e., from the
Digital Operator or by using control circuit terminal signals).

„

Connecting the Load

After confirming that the motor has stopped completely, connect the mechanical system.

Be sure to tighten all the screws when securing the motor shaft to the mechanical system.

„

Operation using the Digital Operator

Use the Digital Operator to start operation in LOCAL mode in the same way as in no-load operation.

If fault occurs during operation, make sure the STOP Key on the Digital Operator is easily accessible.

At first, set the frequency reference to a low speed of one tenth the normal operating speed.

„

Checking Operating Status

Having checked that the operating direction is correct and that the machine is operating smoothly at slow
speed, increase the frequency reference.

After changing the frequency reference or the rotation direction, check that there is no oscillation or abnor-
mal sound from the motor. Check the monitor display to ensure that U1-03 (Output Current) is not too high.

Refer to Adjustment Suggestions on page 4-17 if hunting, vibration, or other problems originating in the
control system occur.