User Parameter Tables

5-

103

Note Attach a Momentary Power Interruption Compensation Unit if compensation for power interruptions of up to 2.0 seconds is required for 208-240Vac

Drives with outputs of 0.4 to 7.5 kW.

* 1. The initial settings for C6-02 are as follows: 0: Low noise PWM, 1: 2.0 kHz, 2: 5.0 kHz, 3: 8.0 kHz, 4: 10 kHz, 5: 12.5 kHz, and 6: 15 kHz. If the carrier

frequency is set higher than the factory setting for Drives with outputs of 5.5 kW or more, the Drive rated current will need to be reduced.

* 2. The initial settings for C6-11 are as follows: 1: 2.0 kHz, 2: 4.0 kHz, 3: 6.0 kHz, 4: 8.0 kHz.

Parameter

Number

Name

Unit

Factory Setting

-

Drive Capacity

kW

18.5

22

30

37

45

55

75

90

110

o2-04

kVA selection

-

9

A

B

C

D

E

F

10

11

b8-03

Energy Saving Control
Filter Time Constant

s

0.50 (Open-loop vector control)

2.00 (Open-loop vector control)

b8-04

Energy Saving Coefficient
Value

-

57.87

51.79

46.27

38.16

35.78

31.35

23.10

20.65

18.12

C6-02

Carrier Frequency Selection

*1

-

6

4

4

4

4

4

4

1

1

C6-11

Carrier Frequency Selection
for Open Loop Vector 2

*2

-

3

3

3

3

3

3

3

1

1

-

Carrier frequency selection
upper limit

-

6

6

4

4

4

4

4

1

1

E2-01

(E4-01)

Motor Rated Current

A

65.8

77.2

105.0

131.0

160.0

190.0

260.0

260.0

260.0

E2-02

(E4-02)

Motor Rated Slip

Hz

1.67

1.70

1.80

1.33

1.60

1.43

1.39

1.39

1.39

E2-03

(E4-03)

Motor No-Load Current

A

15.7

18.5

21.9

38.2

44.0

45.6

72.0

72.0

72.0

E2-05

(E4-05)

Motor Line-to-Line
Resistance

Ω

0.101

0.079

0.064

0.039

0.030

0.022

0.023

0.023

0.023

E2-06

(E4-06)

Motor Leakage Inductance

%

20.1

19.5

20.8

18.8

20.2

20.5

20.0

20.0

20.0

E2-10

Motor Iron Loss for Torque
Compensation

W

505

538

699

823

852

960

1200

1200

1200

L2-02

Momentary Power Loss
Ride-thru Time

s

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

L2-03

Momentary Power Loss
Minimum Base Block Time

s

1.0

1.1

1.1

1.2

1.2

1.3

1.5

1.7

1.7

L2-04

Momentary Power Loss
Voltage Recovery Ramp
Time

s

0.6

0.6

0.6

0.6

1.0

1.0

1.0

1.0

1.0

L8-02

Overheat Alarm Level

°C

90

90

95

100

100

110

100

95

95

n5-02

Motor Acceleration Time

s

0.317

0.355

0.323

0.320

0.387

0.317

0.533

0.592

0.646