Power Loss Ridethrough: L2

User parameters for power loss ridethroughs are shown in the following table.

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

L2-01

Momentary
Power Loss
Detection
Selection

Enables and disables the

momentary power loss
function.

0: Disabled - Drive trips on

(UV1) fault when power is
lost.

1: Power Loss Ride Thru Time

- Drive will restart if power
returns within the time set
in L2-02.*

2: CPU Power Active - Drive

will restart if power returns
prior to control power
supply shut down.*

* In order for a restart to occur,

the run command must be
maintained throughout the
ride thru period.

0 to 2

0

No

A

A

A

A

A

485H

PwrL
Selection

L2-02

Momentary
Power Loss
Ride-thru
Time

Sets the power loss ride-thru
time. This value is dependent
on the capacity of the Drive.
Only effective when L2-01 = 1.

0

to

25.5

0.1sec

*1

No

A

A

A

A

A

486H

PwrL
Ridethru t

L2-03

Momentary
Power Loss
Minimum
Base Block
Time

Sets the minimum time to wait
to allow the residual motor
voltage to decay before the
Drive output turns back on
during power loss ride thru.
After a power loss, if L2-03 is
greater than L2-02, operation
resumes after the time set in
L2-03.

0.1

to

5.0

0.2sec

*1

No

A

A

A

A

A

487H

PwrL
Baseblock t

L2-04

Momentary
Power Loss
Voltage
Recovery
Ramp Time

Sets the time it takes the output
voltage to return to the preset
V/f pattern after speed search
(current detection mode) is
complete.

0.0

to

5.0

0.3sec

*1

No

A

A

A

A

A

488H

PwrL V/F
Ramp t

L2-05

Undervoltage
Detection
Level

Sets the Drive's DC Bus
undervoltage trip level. If this is
set lower than the factory
setting, additional AC input
reactance or DC bus reactance
may be necessary. Consult the
factory before changing this
parameter setting.

150

to

210

*2

190 V

*2

No

A

A

A

A

A

489H

PUV Det
Level