Preventing the Motor from Stalling During Acceleration (Stall Prevention
During Acceleration Function)

The Stall Prevention During Acceleration function prevents the motor from stalling if a heavy load is placed
on the motor, or sudden rapid acceleration is performed.

If you set L3-01 to 1 (enabled) and the Drive output current exceeds the -15% level of the set value in L3-02,
the acceleration rate will begin to slow down. When L3-02 is exceeded, acceleration will stop.

If you set L3-01 to 2 (optimum adjustment), the motor current accelerates to the value set in L3-02. With this
setting, the acceleration time setting is ignored.

„

Related Parameters

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

L3-01

Stall
Prevention
Selection
During Accel

Selects the stall prevention method
used to prevent excessive current
during acceleration.
0: Disabled - Motor accelerates at

active acceleration rate. The
motor may stall if load is too
heavy or accel time is too short.

1: General Purpose - When output

current exceeds L3-02 level,
acceleration stops. Acceleration
will continue when the output
current level falls below the

L3-02 level.

2: Intelligent - The active

acceleration rate is ignored.
Acceleration is completed in the
shortest amount of time without
exceeding the current value set
in L3-02.

0 to 2

1

No

A

A

A

No

No

StallP Accel
Sel

L3-02

Stall
Prevention
Level During
Acceleration

This function is enabled when
L3-01 is "1" or "2".
Drive rated current is 100%.
Decrease the set value if stalling or
excessive current occurs with
factory setting.

0 to 200

150%

No

A

A

A

No

No

StallP Accel
Lvl

L3-03

Stall
Prevention
Limit During
Acceleration

Sets the lower limit for stall
prevention during acceleration, as a
percentage of the Drive's rated
current, when operation is in the
frequency range above E1-06
(constant power region).

0 to 100

50%

No

A

A

A

No

No