5

-18

b5-06

PID Output
Limit

Sets the maximum output
possible from the entire PID
controller. Set as a percentage
(%) of maximum frequency.

0.0

to

100.0

100.0%

Yes

A

A

A

A

A

1AAH

PID Limit

b5-07

PID Offset
Adjustment

Sets the amount of offset of the
output of the PID controller.
Set as a percentage (%) of
maximum frequency.
The offset is summed with the
PID output. This can be used
to artificially kick-start a slow
starting PID loop.

-100.0

to

100.0

0.0%

Yes

A

A

A

A

A

1ABH

PID Offset

b5-08

PID Primary
Delay Time
Constant

Sets the amount of time for
the filter on the output of the
PID controller.
Note: The offset is summed

with the PID output.
This can be used to
artifically kick-start a
slow starting PID loop.

Note: Normally, change is not

required.

0.00

to

10.00

0.00 s

Yes

A

A

A

A

A

1ACH

PID Delay
Time

b5-09

PID Output
Level
Selection

Determines whether the PID
controller will be direct or
reverse acting.
0: Normal Output (direct

acting)

1: Reverse Output (reverse

acting)

0 or 1

0

No

A

A

A

A

A

1ADH

Output Level
Sel

b5-10

PID Output
Gain Setting

Sets the output gain of the
PID controller.

0.0

to

25.0

1.0

No

A

A

A

A

A

1AEH

Output Gain

b5-11

PID Output
Reverse
Selection

0: Zero Limit (when PID

output goes negative,
Drive stops). Zero Limit is
automatic when reverse
prohibit is selected using
b1-04.

1: Reverse (when PID goes

negative, Drive reverses).

0 or 1

0

No

A

A

A

A

A

1AFH

Output Rev
Sel

b5-12

PID
Feedback
Reference
Missing
Detection
Selection

0: Disabled (no detection of

loss of PID feedback)

1: Alarm (detection of loss

of PID feedback,
operation continues
during detection with the
fault contact not
energized)

2: Fault (detection of loss of

PID feeedback, coast to
stop during detection and
fault contact energizes)

0 to 2

0

No

A

A

A

A

A

1B0H

Fb los Det Sel

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2