Emc directive, Installation method – Yaskawa G7 Drive User Manual

Page 438

Advertising
background image

Conformance to UL and CE Markings

10-

15

„

EMC Directive

Varispeed G7-Series Drives satisfy testing for conformance to the EMC Directive under the conditions
described in European Standard EN61800-3.

Installation Method

In order to ensure that the machinery or installation incorporating the Drive conforms to the EMC Directive,
perform installation according to the method below.

Install a noise filter that conforms to European Standards on the input side. (Refer to Table 10.3 EMC
Noise Filters
).

Use a shielded line or metal piping for wiring between the Drive and Motor. Make the wiring as short as
possible.

To suppress harmonics, install a DC reactor in CIMR-G7U20P4, 20P7, 40P4, and 40P7 models. (Refer to
Table 10.4 DC Reactors for Suppressing Harmonics.)

Fig 10.6 Installation Method for Filter and Drive (CIMR-G7U20P4 to 2018, 40P4 to 4018)

L1L2L3PE

IM

L1L2L3 T1T2T3

Remove the paint on the ground side.

Inputs

Filter

Outputs

Drive

Wiring length:

40 cm max.

Metallic plate

Wiring length: 20 m max.

Remove the paint on the ground side.

Advertising